Are Sprinklers Really Required? 12 NFPA Code Questions Designers and Inspectors Keep Asking 

Fire protection requirements rarely match any real world project. Designers, contractors and inspectors often face scenarios not addressed by the code: Is a covered balcony the same as an open porch? The “centerline” of a fire pump is where? Can ESFR sprinklers be spaced closer than 8 feet apart when separated by a beam? In this blog we answer 12 frequently asked questions based on NFPA 13, 13D, 13R, 14, 20 and 25. Each response gives the section it refers to and, where helpful, the reason behind the requirement, so you can use it with confidence on your next project or inspection. 

Description: The question is what is the definition of the “fire pump centerline” for a horizontal split-case centrifugal fire pump as defined in NFPA 20 (2025 edition), Section 4.16.3.2. This reference point is important because it is utilised in calculations involving suction and elevation, such as pressure readings and the height of the water level or supply relative to the pump. The dilemma is whether that centerline is taken at the suction inlet or at the pump impeller (the shaft axis). In a horizontal split case pump these two points can be at different heights as the suction inlet is often located differently to the shaft/impeller axis. So the fundamental question is: what physical reference location does the standard mean by “centerline”? 

 

Question 1.  Section 4.16.3.2 of NFPA 20’s 2025 edition discusses the fire pump centerline. Is the centerline of a horizontal split-case centrifugal fire pump dictated by the suction inlet or the pump impeller?

 

Answer: On a horizontal split-case centrifugal fire pump, the fire pump centerline is the impeller’s centerline, not the pump’s suction inlet.

NFPA 20, 2025 edition, Section 4.16.3.2 states that the requirements of Section 4.16.3.1 do not apply if the supply is a suction tank with its water level at or above the same elevation as the centerline of the fire pump. The gauge pressure at the pump suction flange must not drop below -3 psi (0.2 bar) at 150 percent of rated flow when the tank is at its lowest water level.

The specification specifies “centerline of the fire pump,” not the centerline of the pump’s suction inlet. The centerline of a horizontal split case fire pump is the horizontal geometric axis that runs directly through the center of the pump’s rotating shaft. 

Description: The concern is whether sprinklers are required under an outside projection or canopy more than 4 feet in width in a building that is otherwise completely sprinklered, certainly under NFPA 13 guidelines for exterior projections. The projection has a noncombustible roof and soffit (cement board) and there is no storage under the projection, only furniture. The catch is that the neighbouring external walls are covered with raw wood, a flammable. So the question is whether the noncombustible construction and no storage are adequate to exempt the projection from sprinklers, or if the combustible wall cladding is still the trigger. Briefly, it’s about how the standard addresses combustible exterior walls near to a noncombustible canopy when determining if protection is needed. 

 

Question 2. Is sprinkler protection required beneath an exterior projection or canopy that is more than 4 feet wide in a fully sprinklered building when the ceiling and soffit are made of noncombustible materials (cement board), there is no storage beneath the projection other than furniture, and the adjacent exterior walls are made of untreated wood?

 

Answer: Sprinklers may be omitted in a completely sprinklered structure with an exterior projection/canopy over 4 feet wide, when there is no storage beneath it and the projection itself is noncombustible, even if the building’s outer wall is wood (combustible).

 

In this case, as stated in NFPA 13, 2019 edition, Section 9.2.3.2, sprinklers may be omitted if the exterior canopies, roofs, porte-cocheres, balconies, decks, and similar projections are made of noncombustible, limited-combustible, or fire retardant-treated wood as defined in NFPA 703.

 

This part only requires that exterior canopies, roofs, porte-cocheres, balconies, decks, and similar projections be built with noncombustible, limited-combustible, or fire retardant-treated wood, as defined in NFPA 703. NFPA 703 does not require the outer wall of the building to be noncombustible, limited-combustible, or fire retardant-treated wood.

 

Description: What should an inspector under NFPA 25 do with an outside canopy that seems like it needs sprinkler protection under NFPA 13, but doesn’t have any? The scenario asks if the missing sprinklers should be noted as a deficiency on the inspection report. No. NFPA 25 (Section 1.1.3) assumes the system was installed appropriately and does not require the inspector to investigate for installation or design defects. Such an issue is beyond the scope of its shortcoming as NFPA 25 addresses inspection, testing and maintenance, not design compliance. If the inspector still feels there is something wrong, this should be made as an observation merely, so the owner can be made aware without it being classified as a formal deficiency. 

 

Question 3. During an NFPA 25 inspection, it was discovered that an outside canopy that was needed to be protected by NFPA 13 was not equipped with sprinklers. Should this be considered a deficiency?

 

Answer: No, installation or design faults should not be recorded as deficiencies on an inspection report. Section 1.1.3 clearly addresses this by noting that it is assumed that the system was properly installed and that the standard does not require the inspector to seek for installation or design defects.

 

If an inspector believes something is incorrect, they should record it as an observation only.

Description: This is a question about the NFPA 25 trip test of a dry pipe sprinkler system. How do you choose the test orifice for the distant water-delivery test? The system has mixed sprinkler K-factors (5.6, 8.2, and 14.0). Which K-factor should the test orifice be matched to? Another way to read this is that it must be equivalent to the smallest K-factor installed (K5.6), because that is the smallest hole through which the system is intended to flow. The second reading is that any of the installed K-factors would be ok. The question then becomes whether the standard demands the smallest sprinkler orifice or enables flexibility when different sprinkler sizes are present.

 

Question 4. A dry pipe sprinkler system consists of sprinklers with K-factors of 5.6, 8.2, and 14.0. For the remote water-delivery (trip) test, does the test orifice have to be equivalent to the smallest K-factor installed (K5.6), or can it be equivalent to any of the installed sprinkler K-factors (K5.6, K8.2, or K14.0).

 

Answer: The trip test orifice may be equivalent to any sort of sprinkler installed on the dry system.

 

Given that the connection is meant to replicate the opening of a single sprinkler and that we normally test “worse case” scenarios, it would be reasonable to presume that the orifice is the same as the smallest orifice in the sprinkler system. However, NFPA 13 does not state this explicitly, despite popular belief.

 

Regarding dry-pipe systems, Section 8.17.4.3.1 of the 2013 edition of NFPA 13 (with similar sections dating back at least as far as 1983) states, “A trip test connection or manifold not less than 1-inch in diameter, terminating in a smooth bore corrosion-resistant orifice, to provide a flow equivalent to one sprinkler of a type installed on the particular system, shall be installed.”

Using the wording “of a type installed on the particular system” allows the user to select any size sprinkler orifice, not only the smallest. This differs from wet pipe systems, which must employ an aperture that simulates the smallest sprinkler on the system in the alarm test connection.

 

During the preparation of the 2013 edition of NFPA 13, a proposal was made to amend the requirement to have the orifice simulate the smallest orifice on the system, as is required for wet pipe systems. The committee rejected this motion and issued the following statement:

 

Committee Statement: The standard’s objective is to allow any orifice size on the system. 

 

Description: This topic addresses how the floor zone control rules in NFPA 13R (2022 edition) apply to an apartment block with two connected parts of various heights. The left half is two floors tall, and the right section is three stories tall, linked at the first floor. One option is to have separate zone control assemblies, one for floors one and two of the two-story portion, and another for floors two and three of the three-story portion. The other solution would be that there is no need for separate zone assemblies and the backflow prevention assembly may also be the system control valve. So the question is essentially whether the floor zone regulations apply to a structure with this split height layout or if a single control point is OK. 

 

Question 5. An NFPA 13R-protected apartment building is divided into two portions that are connected on the first floor. The left half is two stories tall, and the right section is three stories tall.

Is the building needed to have separate zone control assemblies, one for the first and second floors of the two-story segment and another for the second and third floors of the three-story section?

 

Alternatively, are separate zone control assemblies unnecessary, allowing the backflow prevention assembly to function as the system control valve?

 

Answer: No, zone control assemblies are not required for each floor or side of the structure. Yes, the mentioned backflow preventor assembly can be used as the sprinkler system’s control valve.

 

NFPA 13R, 2022 edition, Section 6.8.8 states that in multi-story buildings, a control valve per floor is not required. If the building has a combined standpipe and sprinkler system, Section 6.8.10 may need a separate control valve for each story.

 

Section 6.8.6 states that a listed backflow prevention assembly is considered a control valve, and no extra control valve is required. Closed control valves are the leading cause of sprinkler system failures. Because the backflow must be classified for fire protection, both valves in the assembly qualify as sprinkler control valves. There is no reason to install more valves, increasing the likelihood of a closed control valve.

Description: This inquiry is about how sprinkler obstruction laws, possibly NFPA 13’s standards for obstacles to sprinkler discharge, apply to a number of closely spaced objects such as pipes. Individually , each object is smaller than 4 feet broad therefore it would be within the individual-obstruction standards and not the wide-obstructions guidelines . The issue is that the gaps between them are small, thus collectively they can impede water distribution much like one enormous obstruction. So the question is what factors — such as the size of the gaps, or the distance between the objects – lead them to be judged as a single obstruction based on their total breadth. Simply said, it’s about when the standard stops treating the objects individually and starts treating the group as a whole. 

 

Question 6. When several impediments, such as pipelines, each less than 4 feet wide, are erected close together with minor gaps between them, should they be classified as a single obstruction based on their cumulative width or as individual obstructions?

 

Answer: The 2013 edition of NFPA 13 does not provide a general rule for treating many minor impediments (≤ 4 feet wide) as a single combined obstruction rather than independent items. The solution is largely subjective, utilising the obstruction performance target mentioned in Section 8.5.5.1:

 

“Sprinklers shall be located so as to minimise obstructions to discharge… or additional sprinklers shall be provided to ensure adequate coverage of the hazard.”

 

In practice, this means that if the tight spacing causes the impediments to operate together and appreciably interfere with discharge, they should be treated as a single obstruction.

It is worth noting that subsequent versions have attempted to address this subject.

 

  • The 2016 edition of NFPA 13 includes an analogous idea; nevertheless, it is vital to recognise that this guidance applies solely to ESFR sprinklers:

 

According to Section 8.12.5.3.3, in order to be considered individual, groups of pipes or similar small obstructions must be at least three times the width of the nearest adjacent pipe, conduit, cable tray, or similar obstruction.

 

  • The 2025 edition of NFPA 13 includes the following new definition:

3.3.144 Non-solid obstruction. An impediment made up of openings that account for at least 30% of its footprint.

 

This new description was established to support the amended requirements for Supplemental Sprinklers, which simply relate to sprinklers under impediments, as outlined in Section 9.5.5.3.3 of the 2025 edition of NFPA 13.

 

While this new definition does not directly apply to the 2013 edition of NFPA 13 and is not a prescriptive requirement for deciding when “group obstructions” are to be regarded as a single obstruction, it can help determine suitable protection for the situation described. 

Description: This question deals with an apartment block designed to the 2019 version of NFPA 13 and if the guidance found in Annex D.2.19.2.1 is applicable to it. NFPA standards typically include annexs that are informational rather than part of the legal requirements, therefore the question is under what circumstances may that annex text be relied upon. It also raises the larger issue of when annexe content in NFPA papers, including NFPA 101, may be utilised to establish compliance. The negative side is in those cases when its use is not permitted, for example when it is viewed as an obligatory requirement or utilised instead of the real code content. Thus, it is about the status of annexe material, and whether it can be an acceptable means of compliance, or just explanatory guidance. 

 

Question 7. An apartment block project is being planned in line with the 2019 edition of NFPA 13.

 

In what circumstances can the advice in Annex D.2.19.2.1 be applied? Furthermore, when can annex content in NFPA standards, including NFPA 101, be used to establish compliance, and when is it not allowed?

 

Answer: In general, annexs to NFPA standards are designed to provide guidance in applying the standard’s requirements. Annex material is not considered legally enforceable or part of the standard unless it has been formally adopted by the jurisdiction. This concept is reinforced by the language used at the introduction of Annex D: “This annex is not part of the requirements of this NFPA document, but is included for informational purposes only.”

Annex D was added to NFPA 13 a few editions ago to offer users with advice on fire sprinkler design or installation criteria found in NFPA 101, the Life Safety Code, but not necessarily in NFPA 13. The language in Section D.1.1 helps to explain this:

 

In certain circumstances, this varying advice is based on descriptions of particular scenarios addressed by NFPA 101. In other circumstances, this differing guidance arises from NFPA 101’s different aim, which is occupant life safety rather than property protection as provided by NFPA 13.

In response to your inquiry on Section D.2.19.2.1 and the sprinkler exemption in small closets (less than 12 square feet in size), NFPA 13 excludes sprinklers in hotel and motel closets (less than 24 square feet) but not in apartment buildings (see Section 9.2.5.1). Section 9.2.5.3 states that sprinkler protection in other closets is determined on the jurisdiction’s accepted laws, ordinances, or standards. Some model building and fire codes exempt specific closets from sprinklers.

 

If the jurisdiction has approved NFPA 101, the exception for closets in apartment buildings applies.

 

If the jurisdiction has not adopted NFPA 101, the installing contractor or designer can request that the authority having jurisdiction (AHJ) allow the use of this NFPA 101 exception for closets under Section 1.5 of NFPA 13 (Equivalency clause). Because this provision is incorporated into a nationally recognised standard (NFPA 101), some AHJs will consider it equal protection. 

Description: According to NFPA 13 is it permissible to space ESFR sprinklers closer than the customary 8-foot maximum, when there is a 27-inch solid beam between them? Minimum separation is to prevent cold soldering , which is the discharge from one sprinkler wetting an adjacent sprinkler and delaying its functioning . This may be a barrier to the beam hence the question is whether a beam that deep qualifies for decreased spacing, or if the 8 foot minimum applies anyway. 

 

Question 8. An apartment block project is being planned in line with the 2019 edition of NFPA 13.

 

In what circumstances can the advice in Annex D.2.19.2.1 be applied? Furthermore, when can annex content in NFPA standards, including NFPA 101, be used to establish compliance, and when is it not allowed?

 

Answer: Yes, however since this prescriptive permission was not incorporated in the 2019 edition of NFPA 13, the AHJ must approve. The 2019 edition of NFPA 13 stipulates in Section 14.2.9.4 that ESFR sprinklers cannot be located fewer than 8 feet apart, and it also does not specify allow for closer spacing if separated by a beam baffle.

 

In the 2022 edition of NFPA 13, this specific configuration was addressed with a new section as follows:

 

Section 14.2.9.4 still stipulates that ESFR sprinklers cannot be placed fewer than 8 feet apart. However, a new part has been introduced to directly handle the scenario presented.

 

The revised section 14.2.9.4.1 states that:

In buildings with unimpeded construction, when sprinklers are completely above the bottom plane of an adjacent solid structural member, the criteria of 14.2.9.4 do not apply to the sprinklers on either side of the solid structural member.

 

This new subsection explains the arrangement described. Because the beam in question extends below the ESFR deflector, the 8-foot minimum distance does not apply.

Because this provision is not included in the 2019 edition, the AHJ must be addressed and approved for the 2022 edition. It’s worth noting that the NFPA 13 installation committee voted unanimously to approve this adjustment. 

 

 

Description: Is supervisory air required by the 2024 edition of NFPA 14 for a Class I manual dry standpipe system? A manual dry standpipe is generally empty and has no automatic water supply, and it is supplied with water by the fire department through the fire department connection. The concern is, does the requirement still require supervisory air to monitor the system or does that only apply to automatic dry standpipes .

 

Question 9. Is supervisory air necessary for a Class I manual dry standpipe system in accordance with NFPA 14 2024?

 

Answer: Yes. The 2024 edition of NFPA 14, Standard for the Installation of Standpipe and Hose Systems, adds a need for supervisory air for all dry standpipe systems, including Class I manual standpipes.

 

Section 8.3.2.1, entitled Supervisory Air states:

 

All dry standpipe system pipework must be supervised using supervisory air.

Supervisory air should be kept at a minimum pressure of 7 psi and a maximum pressure of 20 psi.

 

The goal is to keep supervisory pressure in the standpipe pipes so that a loss of pressure can indicate a potential problem with system integrity before the fire department needs the standpipe.

Description: Section 23.4.4.12 of the 2016 edition of NFPA 13 limits the maximum operating pressure of sprinklers in extra-hazard and storage occupancies to 175 psi.

 

Question 10. What is the purpose of this requirement?

 

Answer: Higher operating pressures cause the water to atomise and split down into smaller particles. Full-scale fire testing, which included multiple high-challenge fires (such as rack storage), revealed that water molecules were no longer heavy enough to penetrate the fire plume and reach the fire’s source.

 

This concept is further described in the FAQ section of the NFPA 13, 2016 edition Handbook, which indicates that:

 

Excessive discharge pressures may have a negative impact on the effectiveness of sprinkler discharge under high-challenge fire circumstances. At high pressure, water from the sprinkler orifice hits the sprinkler deflector with high velocity, breaking up into small water droplets. These drops may not have enough momentum to penetrate the fire plume found in extra-hazard and storage fires.

Description: The question is if an enclosed third-floor balcony that opens to the exterior and has an open-style railing may be considered an open attached porch according to NFPA 13D (2010 edition), Section 8.6.4. If it is determined to be a similar structure, it would be exempt from sprinkler protection. The question is whether the covered but open balcony layout falls inside that exemption or whether it needs to be sprinklered because it is not a porch in the way the section intends it. 

 

Question 11. We have a project that includes a covered balcony on the third floor; the balcony’s sides are exposed to the external and have an open style railing. Would this be deemed a similar construction to an open attached porch under NFPA 13D, 2010 edition, Section 8.6.4, and hence not require sprinkler protection?

 

Answer: Yes. According to the criteria indicated, the covered third-floor balcony is an open-attached structure, similar to an open-attached porch, and does not require sprinkler protection under Section 8.6.4 of NFPA 13D 2010. Sprinklers are not required in garages, open attached porches, carports, or other similar structures under this provision. The balcony is eligible for this sprinkler omission since its sides are open to the outside, despite having a roof or ceiling atop.

 

This view is reinforced by First Revision No. 10 for the 2022 edition of the NFPA 13D development cycle, which explicitly includes open attached balconies and clarifies that they do not require sprinkler protection.

 

This answer assumes that NFPA 13D is the appropriate installation standard and that no accepted code provision or municipal amendment specifically specifies balcony protection.

Description: According to Section 8.12.5.3.2 of the 2016 edition of NFPA 13, ESFR sprinklers must be set at least 12 inches horizontally from the nearest edge of a bar joist’s bottom chord.

 

Question 12. Is the minimum 12-inch horizontal clearance requirement in Section 8.12.5.3.2 of the 2016 edition of NFPA 13 still applicable when an ESFR sprinkler is installed 4 feet vertically below the bottom chord of a bar joist? The bar joist measures 9 inches in width, and the sprinkler is 10.5 inches horizontally from the bottom chord’s nearest outside border. Please see the attached figure.

 

Answer: Yes, NFPA 13, 2016 edition, Section 8.12.5.3.2 applies even if the bar joist is so deep that the ESFR sprinkler is 4 feet diagonally from the leading edge of the joist’s bottom cord. This rule mandates that the ESFR sprinkler be positioned at least 1 foot horizontally from the nearest edge to any bottom chord of a bar joist or open truss, regardless of the vertical distance between the ESFR sprinkler and the bottom cord of the joist.

 

Closing Thoughts

As these questions illustrate, getting the NFPA standards correct is often a question of details: the edition being used, the precise phrasing of a section, and the distinction between an obligatory requirement and instructional annex material. Requirements also change across editions, as indicated by the ESFR beam spacing and obstruction examples, so always ensure you are checking which edition your jurisdiction has adopted. The authority having jurisdiction (AHJ) is the best resource to consult when the code is silent or confusing. 

Related Articles

Rotaflow- NFPA 13R and the IBC_ Know the Building and Know the Limits

NFPA 13R and the IBC: Know the Building and Know the Limits 

Fire Sprinkler System Design_ 12 Technical Questions and Practical Insights

Fire Sprinkler System Design: Technical Questions and Practical Insights 

Fire-protection-challenges-and-nfpa-guidance

Common Fire Protection Challenges and NFPA Based Guidance