Fire Sprinkler System Design: Technical Questions and Practical Insights 

In designing fire sprinkler systems, various technical aspects, code regulations, and practical hurdles must be taken into account. The NFPA rules must be comprehended since they are a determining factor in the success of the systems’ implementation. Many frequently asked questions concerning components of the process are elaborated within the TechNote FAQs section.

These FAQs provide various relevant issues like ESFR and CMSA systems, sprinkler positioning, hydraulic calculations, storage protection, hazard classes, obstructive requirements, and fire brigade connections.

In each FAQ, there is a particular technical question, followed by the responsible NFPA rules, explaining how they can be applied in the case. Thus, there is no doubt about the usefulness of the information provided in this way.

Description: The current facility was designed with K-14 ESFR pendent sprinklers at a design of 12 sprinklers at 50 psi to protect tyre storage racks up to 25 feet high.

The new owner aims to keep tires on the ground only, to a maximum height of 6 feet. In examining NFPA 13, we  have not seen any ESFR criteria that expressl

Question 1.  Can the existing K-14 ESFR sprinklers be kept and be hydraulically calculated with the applicable area/density criteria for the new floor-storage arrangement?

Answer: Solid stacked or palletised storage of rubber tires is generally not permitted to be protected by ESFR sprinklers. The tire configuration and the tight spacing of the storage piles test the ESFR sprinklers. The natural barriers created by rack uprights and rack shelves aid to restrict fire spread early in the scenario until ESFR sprinklers can establish control or suppression.

 

Two approaches are permitted for ESFR protection of solid piled or palletised storage:

 

  1. Equivalency- The engineer may be able to show the AHJ that they were storing the tires in a comparable fashion with similar flue spacing as the rack storage.
  1. Miscellaneous Storage- If the storage is Miscellaneous Storage, rubber tires may be safeguarded in line with the criteria for Ordinary Hazard.

 

Section 23.1.1 ESFR sprinklers that are designed to comply with any of the criteria in this chapter shall be permitted to protect any of the following:

  1. Light-hazard occupancies
  2. Hazard occupancy, ordinary
  3. Any storage arrangement with OH1, OH2, EH1 and EH2 design standards.

The handbook commentary for this section states that ESFR sprinklers are also permitted to be used for protection of storage arrangements requiring protection as an ordinary hazard Group 1 (OH1), ordinary hazard Group 2 (OH2), extra hazard Group 2 (EH1), or extra hazard Group 2 (EH2) design under the provisions of Chapter 4. 

The design criteria for EH1 and EH2 are very much like those required for additional hazard occupancies, although these storage applications under Chapter 4 would not be subject to a shielding danger as may be the case with some other extra hazard occupancy designs. 

Description: This question deals with the placement of sidewall sprinklers beneath peaked roofs and ceilings. In particular, may sprinklers be located up to 3 feet below the pinnacle of the roof? It also addresses the scenario when the ceiling is skylight glass instead of a normal ceiling. It also includes instances where the skylight glass is inclined or tilted. 

Question 2.  Can sidewall sprinklers be installed a maximum of 3 feet below peaked roofs and ceilings like a skylight with skylight glass as the ceiling? Sometimes the glass is slanted.

Answer: No, ordinary spray sidewall sprinklers can not be put a maximum of 3 feet below a peaked ceiling such as a skylight.

Section 10.2.6.1.3.1 of the 2022 version of NFPA 13 applies only to conventional spray upright and pendent sprinklers. This section shall not apply to sidewall sprinklers.

Standard spray sidewall sprinklers shall be governed by Section 10.3.5. 10.3.5.1.1 for ceilings states that sidewall sprinkler deflectors shall be located no more than 6 inches or less than 4 inches from ceilings unless the conditions of 10.3.5.1.1.2 are met. Section 10.3.5.1.1.2 allows horizontal sidewall sprinklers to be installed 6 in. to 12 in. or 12 in. to 18 in. below noncombustible and limited-combustible ceilings, if they are listed for such usage. 

 

Description: In this facility, opening the main drain does not lower the system pressure sufficiently to automatically start the fire pump. In this case is the fire pump supposed to be manually initiated before or during the main drain test?

The facility has a private fire protection loop with 3 fire pumps and many groups of sprinkler risers.

Question 3. When doing the mandatory main drain test per NFPA 25 on a sprinkler system that is fed by a fire pump, does the fire pump need to be operational during the test?

 

Answer: Yes. During NFPA 25 testing as per Section 4.4, the fire pump shall continue in service unless proper impairment procedures are followed.

The main drain test should be carried out under the same conditions as the original acceptance test so that a thorough comparison of results can be made.The main drain does not have to automatically start the fire pump upon opening. Required fire pump testing specifically checks automatic pump starting. If there is not enough pressure drop over the main drain to start the pump, it may be necessary to start the pump manually or provide some additional flow to simulate the original test conditions.

Where numerous fire pumps are installed, start pressures and sequencing should also be confirmed. Depending on the demand of the system, pumps can be staged or operated concurrently.

If one major drain fails to start any of the fire pumps, the fire pump and jockey pump pressure settings and jockey pump capacity should be checked. But on a big private fire loop with several risers, the flow from a single main drain may simply not be enough to achieve the required pressure drop to start a pump.

Description: This question is regarding mandatory deflector placement for K-16.8 ESFR pendent sprinklers below obstructed roof structure. It examines a roof structure with 12 in. deep purlins. The topic is should the sprinkler deflectors be located 6 to 14 inches below the roof deck. Or it verifies that they can be installed 1 to 6 inches below the bottom of the purlins. 

 

Question 4. If the roof construction has 12-inch-deep purlins and K-16.8 ESFR pendent sprinklers are being placed, do the sprinkler deflectors have to be 6 to 14 inches below the deck?

 

Or the sprinklers may be put with the deflectors 1 to 6 inches below the bottom of the purlins.

Answer: Yes, under certain conditions ESFR sprinklers can be installed 1 to 6 inches below the bottom of the structural member regardless of distance to deck. But there was insufficient information to answer with certainty.

NFPA 13 2025 addresses this in Section 14.2.9.1.2 which notes the choices for ESFR sprinkler deflector spacing under obstructed construction.

If the ceiling is flat and the 12” purlins are solid, then Section 14.2.9.1.2 would apply. This provision shall apply where the roof slope is a maximum of 1 in 12 and the purlins are ’50 percent or less solid.

In section 3 there are 3 alternatives and as the purlins are 12 inches deep option (2) would be relevant and answer the question:

(2) Sprinkler deflectors shall be permitted to be fitted in a horizontal plane not more than 6 inches vertically below the bottom of structural members.

This option would permit the 16.8 K ESFR sprinkler to be set 1 to 6 inches below the bottom of the structural member regardless of distance to the deck.

Where the arrangement is different (roof not flat or purlins more than 50% open), further portions of 14.2.9.1.2 should be referred to.

Description: This question addresses the NFPA 13, 2025 edition requirement for expanding light hazard sprinkler systems to 78,000 sq ft under certain scenarios. It explicitly explores the relationship of these regulations to conventional hazard occupancy locations. The question is whether conventional hazard areas designated as “minor rooms” may be incorporated inside a light hazard system. It asks for clarification on the relation between minor rooms and the permissible growth of the system size.

 

Question 5. NFPA 13, 2025 ed. section 4.4.1 allows light hazard systems to be extended to 78,000 square feet under certain conditions. The question is concerning ordinary hazard “minor rooms”.

Answer: New. NFPA 13, 2025 edition, 4.4.1(2). It does not answer the question for your particular scenario. Earlier editions capped mild and ordinary dangers at 52,000 square feet each.

 

The standard, however, is to follow the guidelines of Section 4.4.3. This section states that when single systems protect extra hazard, high piled storage or storage covered by other NFPA standards, and ordinary or light hazard areas, the extra hazard or storage area coverage shall not exceed the floor area specified for that hazard and the total area coverage shall not exceed the area specified for the lesser hazard.

In this scenario, the aim of the standard is to limit the system size to a maximum of 78,000 square feet, with the ordinary hazard area(s) within that system not exceeding 52,000 square feet. Ordinary hazard space(s) are authorised in the larger light hazard occupancy if the individual occupancy-based system limits are met.

Description: This question addresses the hydraulic design requirements for in-rack sprinklers in multi-row rack storage configurations. It contemplates storage up to 12 feet high within a 22-foot-high structure, with solid shelves measuring more than 64 square feet. The stored commodities are composed of exposed, nonexpanded Group A plastics. The key difficulty is finding the proper hydraulic design criteria for the in-rack sprinkler system when Section 25.2.1.4.1 does not appear to apply. 

 

Question 6. What hydraulic design criteria should be used for in-rack sprinklers in a 22-foot-high structure with storage up to 12 feet high, multi-row racks with solid shelves more than 64 square feet, and exposed, nonexpanded Group A plastics?

Section 25.2.1.4.1 does not appear to be applicable to this arrangement.

Answer: The answer is determined by the height of the Group A plastics storage and the type of sprinkler technology used.

For Group A plastics up to five feet tall:

The in-rack fire sprinkler design relies on four sprinklers that flow at least 22 gallons per minute (gpm). Here’s the language from Section 25.2.2.2:

Where in-rack sprinklers are installed in compliance with this section to safeguard low-piled rack storage of Class I to Class IV commodities up to and including 12 feet (3.7 m) in height and low-piled rack storage of Group For plastic commodities up to and including 5 feet (1.5 m) in height, the in-rack sprinkler design must be based on the hydraulically most demanding four neighbouring in-rack sprinklers, with a minimum flow of 22 gpm (83 L/min) from the hydraulically most remote in-rack sprinkler.

For Group A plastics that exceed 5 feet in height:

The in-rack design is based on the sprinkler technology used.

  • For CDMA sprinklers, see Table 25.4.1.1 – Group A plastics – solid shelves – up to 25 feet – 1 level equals 8 sprinklers at 30 gpm.
  • For CMSA sprinklers, see Table 25.5.1.3 – Group A plastics – solid shelves – up to 25 feet – 1 level = 8 sprinklers at 30 gpm.
  • For ESFR sprinklers, see Table 25.6.2.3 – Group A plastics – solid shelves – up to 40 feet – 1 level equals 8 sprinklers at 30 gpm.

 

Chapter 25 also discusses various space and coverage limits that must be addressed. Section 25.7 provides further protection choices. 

Description: This topic concerns the ESFR sprinkler design requirements for a new building extension intended for high-piled storage. It considers storing exposed, non-expanded polymers in single-, double-, and multi-row racks with a roof deck height of 30 feet 2 1⁄2 inches. The primary worry is the major shift in sprinkler design parameters as the deck height approaches 30 feet. The study investigates if adding 3 inches of noncombustible insulation beneath the roof deck can reduce the effective deck height to 30 feet or below. 

 

Question 7.  We have a new building expansion, and the owner is now requesting a large storage system. They may hold exposed unexpanded plastics in single, double, or multi-row racking. The maximum height of the deck is 30′-2 1/2″.

 

Table 23.3.1 shows a significant increase in design criteria after you exceed 30 feet. Can the GC install 3 inches of noncombustible insulation to the bottom side of the roof deck, lowering the deck height to 30 feet or less and allowing us to apply K16.8 @ 35psi design criterion, for example?

 

Answer: Yes. NFPA 13 allows roof height to be measured to the underside of insulation laid directly against the roof deck. If 3 inches of insulation reduces the measured height to 30 feet or less, the K16.8 ESFR criterion at 35 psi may be applicable, assuming it applies to the commodity, storage arrangement, storage height, and sprinkler listing.

A comparable idea is to create a flat, horizontal dropped ceiling below a storage roof with a slope greater than 2 in 12, followed by sprinklers beneath that ceiling. NFPA 13 recognises this method for storage occupancies, subject to ceiling construction and uplift restrictions. It can also bring the ceiling height in line with a specified design criterion. Both choices are useful but sometimes overlooked.

Description: We are searching for clarity on NFPA 13 Section 10.2.7.2.1.5 from the 2019 version, specifically the term “one-half the allowable distance between sprinklers.”

Table 10.2.4.2.1(b) allows for a maximum sprinkler spacing of 15 feet and a maximum coverage area of 130 square feet in an Ordinary Hazard system with standard spray pendent sprinklers.

Question 8.  When applying Section 10.2.7.2.1.5, is the “allowable distance between sprinklers” based on the table’s maximum spacing of 15 feet, allowing up to 7.5 feet from the midline of the obstruction?

Or does it depend on the actual sprinkler spacing utilised in the layout?

For sprinklers spaced 13 feet × 10 feet, is the allowed distance from the obstacle centerline 7.5 feet based on the table maximum or 6.5 feet depending on the actual 13-foot spacing?

In short, does “allowable distance between sprinklers” refer to the table’s maximum spacing or the space used in the layout?

Answer: The sprinkler installation must comply with the standard’s maximum spacing and maximum area of coverage criteria, as well as any applicable obstruction limitations.

Yes, when applying Section 10.2.7.2.1.5, the maximum permitted distance between sprinklers for ordinary danger is 15 feet, which means that the sprinklers can be up to 7.5 feet from the obstruction’s midline. However, the maximum area of coverage for average hazard remains at 130 square feet per sprinkler.

According to NFPA 13, 2019 edition, Section 10.2.7.2.1.5, as an obstruction rule for sprinkler discharge pattern development, sprinklers may be spaced on opposite sides of the obstruction no more than 4 feet apart, provided the distance from the centerline of the obstruction to the sprinklers does not exceed one-half the allowable distance between sprinklers.

Under this example, to meet this obstruction criterion under ordinary danger, the sprinkler might be set up to 7.5 feet from the midline of the obstacle smaller than 4 feet wide, without the need for an additional sprinkler below the obstruction.

The sprinkler(s) must still cover a maximum area of 130 square feet. In your scenario, if the sprinkler(s) are located 7.5 feet from the obstruction’s centerline, the maximum spacing in the opposite direction will be limited to 8.67 feet to guarantee that the maximum area of coverage of 130 square feet for ordinary danger is not exceeded. 

 

 

Description: This question addresses the fire sprinkler protection standards for Class IV commodities held on moveable racks. It considers a storage configuration with a maximum storage height of ten feet. The primary challenge is determining the most appropriate hazard classification for this sort of storage. Specifically, it investigates whether Ordinary Hazard Group 2 protection is appropriate for the suggested moveable rack storage configuration.

Question 9.  A project includes Class IV commodities kept on movable racks up to a height of 10 feet.

Based on these precautions, would Ordinary Hazard Group 2 protection be enough for this storage arrangement?

Answer: Yes, based on the information supplied, and because the storage in question does not exceed 12 feet in height, it fulfils the criteria of low-piled storage in Section 3.3.118. Furthermore, because this definition clearly refers to “rack storage” and mobile racks are a sort of “rack storage,” this definition would be appropriate.

Section 20.1.1 goes on to state that low-piled storage that meets the criteria in Chapter 4 will be protected by the occupancy hazard criterion in Chapter 4.

Section 4.3.1.7.1 outlines the appropriate protection of low-piled storage protected by ceiling sprinklers, and Table 4.3.1.7.1 specifically states that Class IV commodities stored on multiple racks (as you mentioned, Section 20.5.2 states that moveable racks must be protected in the same way as multiple row racks) and up to 10 feet high are to be protected as an Ordinary Hazard Group 2 occupancy.

Description: This subject concerns the usage of design area reductions for an Extra Hazard Group 1 (EH1) sprinkler system. It takes into account a design density of 0.249 gpm/ft², sprinkler spacing of 130 square feet, and a design area of 3,800 square feet. The key question is whether high-temperature sprinkler and K11.2 sprinkler reductions may be used simultaneously. It requests clarity on whether NFPA 13 allows the combination of these two reductions under the given design parameters. 

 

Question 10.  Can we apply both the high temperature and K11.2 25% reductions for an EH1 with 130 square feet spacing and 0.249 gpm/ft2 design area curves at 3,800 feet?  

Answer: No, you cannot combine the high temperature and K=11.2 reductions.

NFPA 13, 2019 edition, Section 19.3.3.2.7 states that when K-11.2 or larger sprinklers are used with Extra Hazard Group 1 or Extra Hazard Group 2 design curves, the design area may be reduced by 25% but not below 2,000 square feet, regardless of temperature rating.

 

Section 19.3.3.2.8 for multiple adjustments specifies that if multiple adjustments to the area of operation are required in accordance with Sections 19.3.3.2.3, 19.3.3.2.4, 19.3.3.2.5, or 19.3.3.2.6, these adjustments must be compounded based on the area of operation initially selected from Figure 19.3.3.1.1.

Section 19.3.3.2.8 notably eliminates a reference to Section 19.3.3.2.7 for the K=11.2 sprinkler decrease, thus it cannot be compounded.

This was stated clearly in the 2025 version. Section 19.2.3.2.7 for Extra Hazard Occupancies states that for extra hazard occupancies with ceilings not exceeding 30 feet in height, the system area of sprinkler operation may be reduced by 25% without changing the density, but not to less than 2,000 square feet if one of the following conditions occurs:

  1. High-temperature sprinklers are used.
  2. Sprinklers with a K-11.2 (160) rating or larger are used.

Section 19.2.3.2.7.2 goes on to explain the 25% reduction allowed under Section 19.2.3.2.7.1 may only be applied once. 

Description: The owner’s commissioning agent has informed us that fire protection pipes, hangers, and related components may not come into contact with piping, insulation, or other components from adjacent trades.

NFPA 13 addresses the requirement that sprinkler piping not bear the load of other systems, but it does not appear to explicitly forbid unintentional contact.

Question 11.  If both systems are independently supported, is there an NFPA 13 issue with sprinkler pipe just touching another trade’s piping or insulation, as long as no load is transferred to the sprinkler system?

Answer: There is nothing in NFPA 13 or NFPA 25 that precludes sprinkler pipework from coming into touch with piping, insulation, or other trade-related products.

Both standards focus on proper sprinkler system support and restrict the support, hanging, or attachment of other materials or systems to sprinkler piping unless specifically approved. Incidental contact is normally permitted if both systems are supported independently and no load is transferred to the sprinkler pipes or hangers.

Other potential difficulties to consider include corrosion, electrical or grounding issues, material compatibility, and movement caused by seismic activity or thermal expansion.

This should not always be applied to CPVC plumbing. If other materials come into contact with CPVC, you should approach the pipe manufacturer to ensure chemical and material compatibility.

Description: This question is related to the fire department connection (FDC) regulations for ESFR and CMSA sprinkler systems. It looks at how many FDC inlets are necessary for systems that require a 2,500-gpm fire pump. The major question is if two connections are enough, or if four or more connections are needed. It also tackles the proper pipe size for a standalone FDC for larger sprinkler systems, notably whether a 4-inch pipe is sufficient. 

 

Question 12. What is the required number of outlets for an FDC on an ESFR / CMSA system? If a 2,500-gpm pump is required, will four or more connections be needed? Are two adequate?

 

If this FDC must be freestanding, is 4-inch piping adequate for larger systems?

Answer: NFPA 13 specifies that the FDC requires only two 2 ½ inch inlets, independent of sprinkler system type or presence of a fire pump. In addition, the fire department requires a pipe size of 4 inches.

According to the 2022 edition of NFPA 13, these standards are included in Section 16.12.

Section16.12.3.1 specifies that the FDC should have two 2 ½ inch connections. NFPA 13 contains no sections that need greater than two inlets.

Section 16.12.2 (1) specifies that the pipe size to the FDC must be at least 4 inches. NFPA 13 only mandates a bigger pipe size when the FDC is likely to be used by a fire boat (16.12.2 (2)). Even if the FDC is remote (freestanding) and serves a larger system, a 4-inch pipe to the FDC meets NFPA 13 standards.

Annex section A.16.12.4 explains why NFPA 13 requires only two 2 ½ inch inlets and a 4-inch pipe, regardless of system demand.

The aim of a fire department connection is to add pressure to an automatic fire sprinkler. It is not intended to size the fire department connection piping according to system demand.

Unlike NFPA 14 for Standpipes, the Fire Department Connection is meant to complement the sprinkler system’s pressure rather than to fulfil system demand.

 

It should be noted that NFPA 13 specifies the minimum criteria, and the project engineer may request extra FDC inlets and/or a larger pipe depending on the circumstances of the project. 

Closing Thoughts

The topics covered in the FAQs highlight the significance of understanding both the technical specifications and practical usage of the NFPA standards in fire sprinkler system design.

By reviewing these questions, we hope that you gain insights and clarity on common areas of uncertainty in these matters and serve as a reliable source in dealing with any similar challenge while working on any real-life project.

We emphasize that sharing technical knowledge and discussing practical problems is key to being able to create an understanding of the fire protection system in practice.

Related Articles

Rotaflow- NFPA 13R and the IBC_ Know the Building and Know the Limits

NFPA 13R and the IBC: Know the Building and Know the Limits 

Fire-protection-challenges-and-nfpa-guidance

Common Fire Protection Challenges and NFPA Based Guidance

Data Center Fire Protection Economics What Owners and Operators Need to Know

Data Center Fire Protection Economics:What Owners and Operators Need to Know

Understanding NFPA 13 Requirements for Miscellaneous, Low-Piled Storage, and Idle Pallets

Understanding NFPA 13 Requirements for Miscellaneous, Low-Piled Storage, and Idle Pallets

Rotaflow building at sunset

Need Help With Your Project?

From scoping and detailed design to construction and maintenance, if you’ve got questions or ideas you would like to share, send a message.