Affordable housing is a top concern in many communities, and keeping building costs low while maintaining safety has never been more important. NFPA 13R can help because it prioritises life safety and permits sprinklers to be excluded in areas such as empty attics, flammable concealed spaces, shafts, and small closets and bathrooms. However, this reduced protection comes with a catch: many of the design advantages granted by the International Building Code (IBC) to NFPA 13 systems are not applicable when 13R is applied. This might cause confusion among design experts, AHJs, and builders, and in some situations, it may rule out 13R outright. In this episode of TechNotes, we examine five common scenarios in which the decision between 13 and 13R affects what the IBC allows: permissible area, building height, sleeping unit separations, combustible concealed areas, and occupancy separation.
Choosing NFPA 13R: Which Buildings Qualify and What Don’t
With affordable and readily available housing being a top priority in many communities, lowering building costs while preserving occupant safety is more critical than ever. With a primary focus on life safety, using NFPA 13R for fire sprinkler protection in low-rise residential occupancies offers numerous potential cost-saving benefits. Sprinkler protection may be omitted in locations such as attics not used for occupancy or storage, flammable concealed spaces, shafts, smaller housing unit closets and bathrooms, and more. Many of these areas are required to be safeguarded under NFPA 13. Because NFPA 13R provides less protection than NFPA 13, many of the design advantages granted in the International Building Code (IBC) for employing an NFPA 13 system are not applicable when using NFPA 13R. This can cause confusion among many parties in the building and design process, including design professionals, authorities having jurisdiction (AHJ), and contractors alike. Understanding when the building design may limit or even prohibit the use of 13R is critical.

Staying Within Allowable Area When Using NFPA 13R
The IBC specifies how large a building’s area can be dependent on how it is constructed and operated. The code defines these as construction type and occupancy classification. In many circumstances, after that limit is determined in square feet, the code allows for a potential 200% to 300% increase in a building’s permissible area when an NFPA 13 system is implemented. This ‘area increase for sprinklers’ is not permitted when a 13R system is employed. It is often cost effective to separate two or more buildings with strong passive fire protection, such as a structurally independent fire wall, resulting in multiple buildings within a larger complex. In that instance, each building might potentially use 13R, as long as the permissible area does not exceed the code’s requirements. For more specific information, refer to Section 506 of the International Building Code (2024).

Building Height and the 13R Scope Trap
The NFPA 13R standard only applies to residential occupancies “up to and including four stories in height that are located in buildings not exceeding 60 ft.” While this may appear to be sufficient, caution is advised. While the IBC and 13R continue to largely correlate, with 13R permitting up to four floors, the 2021 and 2024 editions of the IBC made significant revisions that influence the use of 13R. Beginning with the 2021 IBC, the use of 13R is limited to four storeys in height, or 30 feet or fewer from the highest occupied floor to the lowest level of fire department access. With current multifamily structures being slightly taller than in the past, 13R may only be eligible in a three-story building. Fast forward to the 2024 edition of the IBC, and the 13R floor threshold for R2 occupancies (apartment buildings) has been raised slightly to provide for 13R protection on a typical four-story building. The revised standard is 45 feet or less from the highest roof elevation to the lowest level of fire department access, or approximately 34 feet to the floor height in a typical building. This requirement remains unchanged in the IBC’s freshly published 2027 edition. While there are other instances, such as podium applications, it is critical to be cognisant of situations like the latest IBC revisions, which may conflict with the classic application and scope of 13R. For more specific information, see Section 903.3.1.2 of the International Building Code (2024).

Dwelling and Sleeping Unit Separations: NFPA 13 vs. NFPA 13R
In many cases, the IBC requires a one-hour fire separation between sleeping and residential units, however with the added protection offered by an NFPA 13 system, the code allows for a reduction to 30 minutes. This can be a significant design benefit, but be aware that if a 13R system is used, the 30-minute reduction is not permitted, and the full one-hour fire separation is still required. This can have an impact on both the vertical and horizontal separations between sleeping or living spaces. Next, we’ll look at another weakness associated with these similar separations: how they’re meant to address any hidden space they travel through. For more specific information, see Sections 420.2, 708.4.3, and 718 of the International Building Code (2024).

Combustible Concealed Spaces and the 13R Catch
One of the most notable distinctions between NFPA 13 and 13R is the permissible removal of protection in combustible concealed spaces when employing 13R. While this might make design and installation easier, take care when designing concealed rooms with residence or sleeping unit separations. If sleeping or dwelling unit separations do not extend all the way through a floor/ceiling assembly or attic, the IBC requires draftstopping and possibly fireblocking; however, if we have an NFPA 13 system or an NFPA 13R system that includes sprinkler protection in these spaces, we can omit these elements. According to the IBC, this would result in adding protection to these concealed places ‘as required’ for an NFPA 13 system. This would necessitate some cooperation among all parties to ensure that the goal of the codes and standards for protecting these spaces are met. For more specific information, see Sections 420.2, 708.4.3, and 718 of the International Building Code (2024).

How Your Sprinkler System Changes Occupancy Separation
When a structure contains residential above and non-residential below, the code mandates that the’mixed-use’ area be constructed to address the various threats. While the usage of 13R in a mixed-use occupation is a complex affair involving numerous building design options, one thing is certain: the IBC treats 13R in much the same way as a ‘non-sprinklered’ building when it comes to occupancy separation. In many circumstances, a separated-use design necessitates a 2-hour occupancy gap between a building’s residential element and many other uses, such as a restaurant (A-2) or mercantile use. When an NFPA 13 is installed, the 2-hour separation might be lowered to one hour. No luck if 13R is picked, as the 2-hour separation must be maintained. For more specific information, refer to Section 508.4 of the International Building Code (2024).

Closing Thoughts
While 13R introduces extra risks in the IBC, the type of system employed must be carefully evaluated. There are numerous architectural design options that can impact the eligibility of 13R. These decisions should be made by the “Registered Design Professional in Responsible Charge,” who is usually a qualified engineer or architect, according to the IBC. This means that if you are an AHJ or a sprinkler contractor, you may not be the appropriate party to make decisions about the building’s use or design, such as its size or height, how the walls and floors are constructed, or the amount of separation required to achieve specific design objectives. Before you become “stuck” as the party who picks 13R over 13 for a low-rise residential occupancy, make sure to bring all of the relevant parties together to avoid design and scope concerns later.